Ex (ATEX)
JUMO NESOS R01 LS – Float Switch in Miniature Form (408301)
- Point level measurement via floats and reed contact
- For liquid media unaffected by foam formation, conductivity (permittivity), or pressure ratios
- Temperature range from -52 to +240 °C
- Available in numerous versions
- Approvals and certificates are available for explosion protection, shipbuilding, railway applications, and the Water Resources Act (WHG) as well as a certification for the Pressure Equipment Directive (PED)
JUMO NESOS R02 LS – Float Switch Standard Version (408302)
- Point level measurement via floats and reed contact
- For liquid media unaffected by foam formation, conductivity (permittivity), or pressure ratios
- Temperature range from -52 to +240 °C
- Available in numerous versions
- Approvals and certificates are available for explosion protection, shipbuilding, railway applications, and the Water Resources Act (WHG) as well as a certification for the Pressure Equipment Directive (PED)
JUMO NESOS R20 LT – Level Transmitter via Float (408320)
- Level measurement via float and reed chain
- For liquid media unaffected by foam formation, conductivity (permittivity), or pressure ratios
- Temperature range from -52 to +180 °C
- Available in numerous versions
- Approvals and certificates are available for explosion protection, shipbuilding, railway applications, and the Water Resources Act (WHG) as well as a certification for the Pressure Equipment Directive (PED)
JUMO dTRANS p33 - Pressure Transmitter or Level Probe for Use in Ex-Areas (404753)
- Pressure transmitter or level probe
- ATEX approval
- Measuring ranges: 250 mbar to 600 bar relative and 600 mbar to 25 bar absolute
- Medium temperature: -40 to +85 °C, optionally to 200 °C (SIP and CIP capable)
- Accuracy: 0.5 % MSP (linearity)
- Protection type: IP65
Particularly for the level probe variant (IP68):
- Measuring ranges: 250 mbar to 10 bar (2.5 to 100 mWS)
- Medium temperature: 0 to 50 °C
JUMO exTHERM-DR – Two-State Controller with ATEX and IECEx Approval
- Approval Ex II (1) G [Ex ia Ga] II C, Ex II (1) D [Ex ia Da] III C, Ex II (2) G [Ex eb Gb] IIC, Ex II (2) D [Ex tb Db] IIIC
- Ignition protection type [Ex ia] with intrinsically safe inputs or [Ex e] with increased safety
- Controller output (relay)
- Limit value output (relay) for alarm indication
- Analog output configurable as actual value output, setpoint value output, or logic output 0/10 V for control of solid state relay
- LCD display for process information
- USB interface on front and setup program for simple startup
JUMO safetyM STB/STW Ex – Safety Temperature Limiter/Monitor According to DIN EN 14597 and ATEX Approval
- Ignition protection type [Ex ia] with intrinsically safe inputs or [Ex e] with increased safety
- Approval II (1) (2) (3) G (b1) [Ex ia Ga] (e pz] IIC, II (1) (2) (3) D (b1) [Ex ia Da] (p Dc] IIIC, II (1) (1) (2) G (b2) [Ex ia Ga] (e py] IIC, II (1) (1) (2) D (b2) [Ex ia Da] (p DB] IIIC
- Safety monitor and safety limiter for temperature, pressure, and other process variables
- Configurable universal input
- 1oo2D architecture (2-channel structure with diagnostics channel)
- Approvals according to DIN EN 14597, SIL 3, PL e
- Security-related limit value relay (230 V, 3 A)
- Pre-alarm absolute or adjustable as a margin from the limit value
- Default actual value output
- Compact solution
- Ignition source monitoring according to EN 13463 and EN 50495 SIL 2
- Minimum pressure monitoring SIL 2
JUMO dTRANS T07 – Two-Channel Temperature Transmitter with HART®/Ex/SIL (707080)
- 2 universal measurement inputs (RTD, TC, Ω, mV)
- High degree of accuracy (0.1 K with Pt100 sensor)
- Output 4 to 20 mA (single channel, loop powered)
- 2 enclosure versions (B-head or DIN rail)
- HART® 7 protocol
- SIL 2/3 hardware/software according to IEC 61 508
- Reliable measurement mode through sensor monitoring and device hardware error detection
- Optional plug-on display for B-head device version
JUMO PROCESStemp RTD Temperature Probe for Process Technology with Ex Approval (902820)
- For temperatures from -200 to +600 °C
- With protection tubes made of stainless steel, titanium, tantalum, Inconel®, and HASTELLOY®
- Available with two-wire transmitter (4 to 20 mA/HART®) in Ex version
- II 1/2 G Ex ia IIC T6 ... T1 Ga/Gb¹
- II 1/2 D Ex ia IIIC T80 ... T400 °C Da/Db¹
- II 1/2 G Ex ia/d IIC T6 ... T1 Ga/Gb¹
- II 1/2 D Ex ia/tb IIIC T80 ... T400 °C¹
- With interchangeable measuring insert (not for Ex basic types)
¹ See description